In the connection of a water distribution system to water-heating appliances, there is the potential for the
migration of heated water into the water distribution piping. In a typical water distribution system, the water will
expand into the public water service. If the expansion of water is not accommodated in the system, dangerously high
pressures can develop that can cause damage to piping, components and the water heater.
read more
The minimum static pressure at the dwelling entrance for either public or private water service (as determined by the
local water authority) should be 40 psi (276 kPa). The maximum static pressure should be 80 psi (552 kPa). When the
pressure from the public water main or private well exceeds 80 psi, a pressure-reducing valve or regulator should be
installed at the point where the water service pipe enters the dwelling. The pressure regulator should be installed
immediately downstream of the main shut-off valve. To allow a continuous flow of water to the dwelling, the water
pressure-reducing valve is designed to remain in an open position if the component fails.
read more
Condensate drains from air conditioner coils, condensing furnaces, and heat-recovery ventilators should not drain
directly into a DWV pipe. An indirect drain using an air gap should be installed. In some locations, the direct
connection of a condensate drain line into a stack is not permitted, even with a trap. The potential danger is that
sewer gases may enter the house through the condensate drain line. It is not a cross-connection problem, but it is
unsafe and unhealthy. www.nachi.org &
www.apollohome.com
read more
There are deep wells (more than 25 feet deep) and shallow wells (25 feet or less). A typical well pump can pull up
about 25 feet of water. If the well is deeper than 25 feet, the pump will have to be installed at the bottom of the
well to push the water up. Pumps are better at pushing than pulling.
read more
Inspection of private water sources, such as a well, is beyond the scope of a home inspection.
read more
A water heater tank should be installed inside a pan in locations in a dwelling where a leak from the tank could
cause damage to the structure or property. The pan is intended to catch water leaks from the tank or associated
connections, or condensate from the tank. The pan should be made of galvanized steel or other material approved for
that use. Pre-fabricated aluminum and plastic pans are common and widely used. Aluminum and plastic pans may not be
allowed by every authority having jurisdiction (AHJ) or code official because they are not made of galvanized steel,
and some tank manufacturers require the use of a metal pan only.
read more
Hot water boilers should be provided with expansion tanks. There are two types of expansion tanks designated for use
with a residential boiler system. A non-pressurized tank is simply a cylinder filled with air set at atmosphere
pressure. A pressurized tank is a sealed cylinder divided by a flexible diaphragm. An expansion tank provides space
for the water to expand as it is heated, and it keeps the water pressure within the normal operating range while the
boiler is working. Thank you www.nachi.org
read more
The following are 13 requirements for a discharge pipe serving a TPR valve:
read more
Temperature and pressure-relief (TPR) valves are safety devices installed on water heating appliances, such as
boilers and domestic water supply heaters. TPRs are designed to automatically release water in the event that
pressure or temperature in the water tank exceeds safe levels.
read more
Water circulating through a hot water circulation system becomes chemically inert and does not rust the piping. But
water heaters have a constant supply of fresh water with lots of corrosion-causing oxygen. Because of this, water
heaters are prone to corrosion. As a result, water heaters usually have an anti-corrosion rod or sacrificial rod
installed. Sacrificial anodes are typically made of magnesium or aluminum. The rod is immersed inside the water
heater tank, allowing the chemical reaction from the fresh water to attack it rather than the tank. In some areas,
rods are replaced regularly.
read more